FlexStat 1 Operation Guide, Rev. R
Operation Guide
FlexStat
BACnet Programmable Thermostats
Contents
Overview ................................................................3
Applications and Installation ...................................3
Operation (Basic) .................................................... 4
Navigation ..........................................................4
Room Temp. Setpoint Adjustment .......................4
H/C, Fan, Occupancy, and Override ...................4
Main Menu and Settings ......................................4
Display Options ..................................................5
Configuration (Setup) ..............................................6
Main Menu Overview .........................................6
About the FlexStat ...............................................6
Advanced Menu ..................................................7
(Advanced) Application and Additional Setup .. 7
Auxiliary Heat (Heat Pump Only) Setup ......7
Damper Setup .............................................7
Fan Setup..................................................... 8
Humidity Setup ...........................................8
Motion Sensor Setup ...................................8
Optimum Start Setup ..................................9
Sensor Setup ................................................9
Setback (OAT) Lockout Setup ....................10
Staging Setup .............................................10
Valve Setup ...............................................10
(Advanced) CB (Control Basic) Programs .......10
(Advanced) CO
2
Sensor (and DCV) ................11
CO
2
Sensor Setup and Information ...........11
DCV (Demand Control Ventilation) Setup .11
(Advanced) Communications (BACnet) .......... 14
(Advanced) Date/Time ................................... 16
(Advanced) BACnet Device Properties ........... 17
(Advanced) Inputs ..........................................17
(Advanced) Temp. Setpoint Limits ..................17
(Advanced) PID Loop Configuration ..............18
(Advanced) Restart/Restore ...........................18
(Advanced) Security Levels and Passwords .....18
(Advanced) Test ..............................................19
(Advanced) Trend Logs ................................... 20
(Advanced) User Interface (UI) ......................21
Contrast ....................................................21
Display Blanking .......................................21
Inactivity ...................................................21
Rotation Values ..........................................21
Show Temperature Tenths (Decimals) ........21
Show Time and Date .................................. 21
Mode .........................................................21
Alarms ...............................................................23
Date/Time ......................................................... 23
DCV (Demand Control Ventilation) ..................24
Schedules ..........................................................24
Setpoints ...........................................................25
System Modes ...................................................25
Trend Viewer .....................................................26
Specifications, design, and operation are subject to change without notice.
Zobrazit stránku 0
1 2 3 4 5 6 ... 45 46

Shrnutí obsahu

Strany 1 - Operation Guide

FlexStat 1 Operation Guide, Rev. ROperation GuideFlexStat™BACnet Programmable ThermostatsContentsOverview ...

Strany 2 - (Click for details.)

FlexStat 10 Operation Guide, Rev. RSetback (OAT) Lockout Setup SETBACK LOCKOUTOAT LOCKOUT:LOCKOUT TEMP: 30° FENABLESetback OAT lockout is disabled b

Strany 3 - CAUTION

FlexStat 11 Operation Guide, Rev. R(Advanced) CO2 Sensor (and DCV) CO2 SENSORSENSOR INFOCALIBRATION CO2 SENSOR INFOMODEL: T6615SUB VOL: A15SW DATE:

Strany 4 - Configuration

FlexStat 12 Operation Guide, Rev. RNOTE: Not all applications have a modulating economizer option. Withoutamodulatingeconomizerselected,DCVwil

Strany 5 - Display Options

FlexStat 13 Operation Guide, Rev. Rposition, not the minimum outside air percentage.) The OA damper shall be at this position when Space CO2 is at or

Strany 6 - Configuration (Setup)

FlexStat 14 Operation Guide, Rev. Rnished and returned the ventilation rate to “normal” operation).• Pre-purge—If enabled in the programming (disab

Strany 7 - Advanced Menu

FlexStat 15 Operation Guide, Rev. RRoute StatusStatus Description ActionActive The network is functioning correctly and capable of passing traffic.Non

Strany 8

FlexStat 16 Operation Guide, Rev. R(Advanced) Date/Time DATE/TIMEDATE:TIME: 1:43:59 PMUTC OFFSET: 300DST ENABLE: TRUEDST AUTO: TRUEDST START:>2ND

Strany 9

FlexStat 17 Operation Guide, Rev. R(Advanced) BACnet Device Properties DEVICEINSTANCE:NAME: FlexStat_101LOCATION: KMC Controls1To set the BACnet devi

Strany 10

FlexStat 18 Operation Guide, Rev. R(Advanced) PID Loop Configuration LOOP CONFIGURATIONCOOL PROP:HEAT PROP: 2.0° FCOOL INTG: 0/hrHEAT INTG: 0/hrECON

Strany 11 - Sensor (and DCV)

FlexStat 19 Operation Guide, Rev. R(Advanced) Test TESTLCD/KEY TESTThe test menu merely tests the display’s pixels and key functions (as verication

Strany 12

FlexStat 2 Operation Guide, Rev. RResetting the FlexStat ...26Types of Reset ...

Strany 13

FlexStat 20 Operation Guide, Rev. R(Advanced) Trend Logs TREND LOGSTREND 1:TREND 2: TRUETREND 3: FALSETREND 4: FALSETREND 5: FALSETREND 6: FALSETREN

Strany 14

FlexStat 21 Operation Guide, Rev. R(Advanced) User Interface (UI) USER INTERFACECONTRASTDISPLAY BLANKING: NOINACTIVITY (SECS): 60ROTATION VALUESSHOW

Strany 15

FlexStat 22 Operation Guide, Rev. RFor Hospitality mode, Setpoint Control conguration options are Single Setpoint or Schedule:• SingleSetpoint wil

Strany 16 - (Advanced) Date/Time

FlexStat 23 Operation Guide, Rev. RAlarms SAT 4/11 3:20 PM COOL: OCC: FAN: SERVICE HUM: 20%R

Strany 17 - (Advanced) Inputs

FlexStat 24 Operation Guide, Rev. RSchedules SCHEDULEENTIRE WEEK [MON–SUN]WEEKDAYS [MON–FRI]WEEKEND [SAT–SUN]INDIVIDUAL DAYSHOLIDAYS ENTIRE WEEK1:2:

Strany 18 - (Advanced) Restart/Restore

FlexStat 25 Operation Guide, Rev. RSystem Modes SYSTEMSYSTEM ENABLE:OCC OVRIDE (HRS): 1.0AUTOThis menu allows changes to system enable (auto, o, hea

Strany 19 - (Advanced) Test

FlexStat 26 Operation Guide, Rev. RTrend Viewer TREND VIEWER1:2: SPACE HUMIDITY 273: FAN 194: COOL 1 185: COOL 2 2

Strany 20 - (Advanced) Trend Logs

FlexStat 27 Operation Guide, Rev. RA coldstart does the following in the FlexStat:• (Afterzeroingoutobjectsduringtherestartprocess)returns

Strany 21

FlexStat 28 Operation Guide, Rev. RMS/TP Network CommunicationConnect the EIA-485 MS/TP network wiring and set the EOL switches accordingly. (See the

Strany 22 - COOL

FlexStat 29 Operation Guide, Rev. RFirmware UpgradeThe existing version of rmware can be viewed from the About the FlexStat screen. (See About the F

Strany 23 - Date/Time

FlexStat 3 Operation Guide, Rev. ROverview Applications and Installation1. Wire the FlexStat’s backplate to the desired equipment and set the FlexS

Strany 24 - Schedules

FlexStat 30 Operation Guide, Rev. RTroubleshootingAlarm IssuesAlarm, (False) Fan Fail• Check conguration. Be sure the Fan Status option is not sele

Strany 25 - Setpoints

FlexStat 31 Operation Guide, Rev. R• Reduce the Max Master number down to the minimum needed for that network—see (Ad-vanced) Communications (BACnet

Strany 26 - Resetting the FlexStat

FlexStat 32 Operation Guide, Rev. RDisplay Is Blank (or Erratic)• If the display comes on when a buon is pushed, Display Blanking is enabled. (See

Strany 27 - Restore Factory

FlexStat 33 Operation Guide, Rev. RCustom Programming and Web IssuesControl Basic Programs Do Not WorkNOTE: The FlexStat has a library of built-in a

Strany 28 - Network Connection

FlexStat 34 Operation Guide, Rev. RCO2 Level Is “Too High”• See the CO2 and DCV Sequences Are Not Work-ing section above.• To reduce nuisance compl

Strany 29 - Accessories

FlexStat 35 Operation Guide, Rev. RAlso check that its leads are not pinched, shorted, or broken and that the tape holding down the leads is not loos

Strany 30 - Alarm, (False) Fan Fail

FlexStat 36 Operation Guide, Rev. ROutput, Fan, and Relay IssuesAnalog Output Does Not Work CAUTIONDo not mistakenly connect 24 VAC to an analog outp

Strany 31 - Cover Binds on Backplate

FlexStat 37 Operation Guide, Rev. RRelay (Internal) Does Not Work CAUTIONRelays are for Class-2 voltages (24 VAC) only. Do not connect line voltage t

Strany 32 - “SYSTEM ERROR” Is Displayed

FlexStat 38 Operation Guide, Rev. R• If the USBportdoesnotappearinthedrop-downlist, close the tool, remove power to the FlexStat, disconnect

Strany 33

FlexStat 39 Operation Guide, Rev. RWiring IssuesInstallation Wiring Considerations CAUTIONTo avoid damage from ground loops and other communication i

Strany 34

FlexStat 4 Operation Guide, Rev. ROperation (Basic)NavigationNavigatethemenusandchangeseingsbypress-ingacombinationofvariousarrowbuon

Strany 35

FlexStat 40 Operation Guide, Rev. RImportant NoticesThe KMC logo and TotalControl are registered trademarks and BACstage is a trademark of KMC Contro

Strany 36 - Fan Does Not Run

FlexStat 41 Operation Guide, Rev. RReferenceCommonacronymsandabbreviations in FlexStat and related documents include:amp = amperesA = amperesAAC =

Strany 37 - Firmware Upgrade Failures

FlexStat 42 Operation Guide, Rev. RFor denitions of various terms in this document, refer to the award-winning pocket-sized GreenBuildingandCon-t

Strany 38

FlexStat 43 Operation Guide, Rev. RIndexAAbbreviations: 41About the FlexStat: 6Access Levels, Password: 18Accessories: 29Acronyms: 41Adapter Bac

Strany 39 - Wiring Issues

FlexStat 44 Operation Guide, Rev. RDetector. See Motion SensorDeviceInstance: 6, 17, 27, 28Properties: 17Diagnostics, MS/TP: 15Differential, Minim

Strany 40 - Important Notices

FlexStat 45 Operation Guide, Rev. RPParts (Accessories): 29Passwords: 18, 25PC (Network) Data Port: 28PECI (Portland Energy Conservation, Inc.):

Strany 41 - Reference

FlexStat 46 Operation Guide, Rev. R© 2014 KMC Controls, Inc. 913-019-02RKMCControls19476 Industrial DriveNew Paris, IN 46553574.831.5250; Fax 574.

Strany 42 - Definitions of Terms

FlexStat 5 Operation Guide, Rev. R WED 11/19 3:22 PM COOL: OCC: FAN: HUM: 37%

Strany 43

FlexStat 6 Operation Guide, Rev. RConfiguration (Setup)NOTE: MenusshowninthisdocumentreectFIRMWAREVERSIONR2.1.0.9orlater.Actualcontext-

Strany 44

FlexStat 7 Operation Guide, Rev. RAdvanced Menu ADVANCEDAPPLICATIONCB PROGRAMSCOMMUNICATIONDATE/TIMEDEVICEINPUTSLIMITSThe Advanced Menu displays var

Strany 45 - Standby, Motion Sensor: 8

FlexStat 8 Operation Guide, Rev. RWhen BAC-1xxxxx models have an application with the CO2 sensor ANDthemodulatingeconomizeroptionenabled, menu

Strany 46 - New Paris, IN 46553

FlexStat 9 Operation Guide, Rev. Rreverting from Standby back to Occupied mode (although it may still take some time for the room to reach its norma

Komentáře k této Příručce