Kmc-controls CTE-5202W Uživatelský manuál Strana 1

Procházejte online nebo si stáhněte Uživatelský manuál pro Senzory Kmc-controls CTE-5202W. KMC Controls CTE-5202W User Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 4
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
CTE-5202 Electronic Room Thermostat with LCD Display 1 Installation and Operation Guide
1. Ifthethermostatislockedonthebackplate,turn
thetwohexscrews(inthetwo outermost holes)
inthebackplateCLOCKWISEuntilthey(just)
clearthecover.Swingthethermostatupand
awayfromthebackplatetoremoveit.
Installation and Operation Guide
Electronic Room Thermostat with LCD Display
CTE-5202
Installation
Rough-in Preparation
For optimum temperature sensor performance, the
thermostat must be mounted on an interior wall
and away from heat sources, sunlight, windows,
air vents, and air circulation obstructions (e.g.,
curtains, furniture).
Ifreplacinganexistingthermostat,labelwiresas
neededforreferencewhenremovingtheexisting
thermostat.
Completerough-inwiringateachlocationpriorto
thermostatinstallation.Cableinsulationmustmeet
localbuildingcodes.
Installation 1
Rough-in Preparation 1
Mounting and Wiring 1
Operation 2
Change Setpoint 2
Change Configuration 2
External Input (AI1) 4
Maintenance 4
Accessories 4
Additional Resources 4
Important Notices 4
CAUTION
To prevent damage to the board, do not insert
a screwdriver into any holes other than the two
outermost holes. To prevent mounting screw heads
from touching the circuit board in the thermostat, use
only the mounting screws supplied by KMC Controls.
Using other screws may damage the thermostat. Do
not turn screws in farther than necessary to remove
the cover.
2. Routethecablethroughthebackplate.
~
T
T
AI1
AO1
AO2
SET
POINT
A
A B C D E
3.25in. 5.16in. 0.88in. 3.25in. 0.15in.diameter
83mm 116mm 22mm 83mm 3.81mmdiameter
B
C
D
E
Mounting and Wiring
ThethermostatmustNOTbe:
• Mountedonanexteriorwall.
• Mountedonornearalargethermalmass(e.g.,
concreteblockwall).
• Blockedfromnormalaircirculationbyobstruc-
tions.
•
Exposedtoheatsources(e.g.,lights,computers,
copiers,orcoeemakers)ortosunlight(atany
timeoftheday).
• Exposedtodrasfromwindows,diusers,or
returns.
•
Exposedtoairowthroughtheconduit(from
leaksinplenumducts)—putplumberspuyor
similarmaterialinsidetheconduittoblockair
ow.
NOTE: For specications and other information,
see the CTE-5202 Data Sheet.
NOTE: For detailed applications, cross-references,
accessories, and other information, see the
CTE-5202 Applications Guide.
Zobrazit stránku 0
1 2 3 4

Shrnutí obsahu

Strany 1 - CAUTION

CTE-5202 Electronic Room Thermostat with LCD Display 1 Installation and Operation Guide1. Ifthethermostatislockedonthebackplate,turnt

Strany 2 - Operation

CTE-5202 Electronic Room Thermostat with LCD Display 2 Installation and Operation GuideOperationChange SetpointTochangethesetpoint:1. Pusht

Strany 3 - SEQUENCE # 2:

CTE-5202 Electronic Room Thermostat with LCD Display 3 Installation and Operation GuideNOTE: AO1istypicallyusedtocontrolthecool-ingout

Strany 4 - Important Notices

CTE-5202 Electronic Room Thermostat with LCD Display 4 Installation and Operation GuideAccessoriesMaintenanceRemovedustasnecessaryfromholes

Příbuzné modely CTE-5202

Komentáře k této Příručce

Žádné komentáře